STANDARD FEATURES | DESCRIPTION |
---|---|
Human Machine Interface |
5.7″ Touch Screen(s), Color, 640 x 480 pixels, PDF Storage/Data Logging (32 GB SD Card) |
Programmable Logic Control |
PLC provides advanced control logic and system communication |
BMS Communication |
Modbus TCP via Ethernet |
Hood Temperature Monitors |
Resistance Temperature Detectors, Hood Canopy and Exhaust Collar Mounted |
Ambient Temperature Monitor |
Room Ambient Temperature Monitor(s) |
Digital Outputs |
Exhaust and/or MUA Fans, Light Circuit(s), Electrical Gas Valve Circuit(s) |
Analog Outputs |
4-20 mA or 0-10 VDC signals for Variable Speed Motor Control |
FSS Integration |
Upon Fire Suppression System actuation, automatically shunts power to MUA Fans and Electric Gas Valve, powers the Exhaust Fan(s) at 100%. Provides system Alarm Signal and Manual Reset Relay for Gas Valve |
Energy Analysis |
24/7 DCKV Energy Usage and Cost Savings Analysis |
Auto Exhaust Fan Control |
Automatically powers the Exhaust Fan circuit(s) when the RTDs detect elevated temperatures inside of a hood |
Fan Control |
Hood Fans, Off/On 0-100% Variable |
Light Control |
Hood Lights, Off/On |
Enclosure |
Type I Stainless Steel Enclosure(s) |
Alarms |
Local and BMS Alarm Notification with Alarm Logging |
DemandAire Gold
Zonal Temperature Monitoring
1. HMI Wall Mounted (Recessed Shown)
2. Zonal Temperature Monitoring
3. Ambient Temperature Monitoring
4. Wall Canopy Hood
5. Resistance Temperature Detectors
6. Light Fixtures
7. Exhaust Duct
8. Exhaust Fan
9. Access Enclosure
10. Electric Gas Valv
11. Fire Suppression System
12. DemandAire Control Panel
(Cabinet Mounted Shown)
13. Hood Utility Cabinet
14. Fire Suppression System Pull Station
15. Cooking Appliances
16. Variable Frequency Drives (VFDs). DemandAire Gold DCKV Systems require VFDs. The VFDs can be supplied by Streivor or purchased separately. VFDs can be installed inside of the DemandAire control panel or installed in a remote enclosure.